Page 3–34 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “advanCed” menu of parameTers (ConTinued)
P6.5 – Fixed Voltage Hold. Reg. Type:
Description:
Read/Write
Selects the source for the voltage value used in the power calculations.
Range: Modbus Decimal Value: Default (decimal):
Off : kW, kVAR, and kVA are calculated using the internally
measured voltage. This internally measured voltage is not
an accurate method of obtaining a voltage reading, and
can have an error up to 35% if the starter and motor are
unloaded or lightly loaded.
On : kW, kVAR, and kVA are calculated using the “Fixed Voltage.
This voltage level will be displayed on the “Monitor” screen
as Vrms (Approx).
0
1
Off (0)
Modbus Address: Modbus Format:
35264 ( 89C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → iERS → Fixed Voltage
advanCed “ConTrol meThod” parameTer
P7.0 – Control Method Hold. Reg. Type:
Description:
Read/Write
Local Touch Screen : Control using the button on the keypad.
(Digital Inputs are disabled; Digital Outputs still function as configured.)
User Programmable : Control using the terminals; function defined in “I/O” menu.
Two Wire Control : Control using terminals; functions fixed as shown on screen.
Three Wire Control : Control using terminals; functions fixed as shown on screen.
Modbus Network : Control via remote Modbus network, remote touchscreen, or Modbus TCP /
EtherNet/IP. (Digital Inputs are disabled; Digital Outputs still function as configured.)
Range: Modbus Decimal Value: Default (decimal):
Local Touch Screen
User Programmable
Two Wire Control
Three Wire Control
Modbus Network
0
1
2
3
4
Local (0)
Modbus Address: Modbus Format:
59392 ( E800 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Control Method
(also Home → Auto Setup → Control Method) (also Home → I/O → Digital Inputs → Control Method)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals