Page 3–34 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “advanCed” menu of parameTers (ConTinued)
P6.5 – Fixed Voltage Hold. Reg. Type:
Description:
Read/Write
Selects the source for the voltage value used in the power calculations.
Range: Modbus Decimal Value: Default (decimal):
• Off : kW, kVAR, and kVA are calculated using the internally
measured voltage. This internally measured voltage is not
an accurate method of obtaining a voltage reading, and
can have an error up to 35% if the starter and motor are
unloaded or lightly loaded.
• On : kW, kVAR, and kVA are calculated using the “Fixed Voltage.”
This voltage level will be displayed on the “Monitor” screen
as Vrms (Approx).
• 0
• 1
• Off (0)
Modbus Address: Modbus Format:
35264 ( 89C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → iERS → Fixed Voltage
advanCed “ConTrol meThod” parameTer
P7.0 – Control Method Hold. Reg. Type:
Description:
Read/Write
• Local Touch Screen : Control using the button on the keypad.
(Digital Inputs are disabled; Digital Outputs still function as configured.)
• User Programmable : Control using the terminals; function defined in “I/O” menu.
• Two Wire Control : Control using terminals; functions fixed as shown on screen.
• Three Wire Control : Control using terminals; functions fixed as shown on screen.
• Modbus Network : Control via remote Modbus network, remote touchscreen, or Modbus TCP /
EtherNet/IP. (Digital Inputs are disabled; Digital Outputs still function as configured.)
Range: Modbus Decimal Value: Default (decimal):
• Local Touch Screen
• User Programmable
• Two Wire Control
• Three Wire Control
• Modbus Network
• 0
• 1
• 2
• 3
• 4
• Local (0)
Modbus Address: Modbus Format:
59392 ( E800 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Control Method
(also Home → Auto Setup → Control Method) (also Home → I/O → Digital Inputs → Control Method)