Chapter 3: Configuration and Parameters
Page 3–61Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “log” menu of parameTers (ConTinued)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
P16.6 – Event Time –
Last Peak Start Current / Last Temperature / Last Overload -6
Holding
Register Type:
Description:
Read Only
Displays the event time -6.
Range: Modbus Decimal Value: Default:
hh:mm:ss Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
GMT
Modbus Address: Modbus Format:
38482 ( 9652 hex ) 6 Bytes
Touchscreen Menu Path:
Home → Log → Start Current / Temperature / Overload →
Last Peak Start Current / Last Temperature / Last Overload -6
P16.7 – Event Time –
Last Peak Start Current / Last Temperature / Last Overload -7
Holding
Register Type:
Description:
Read Only
Displays the event time -7.
Range: Modbus Decimal Value: Default:
hh:mm:ss Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
GMT
Modbus Address: Modbus Format:
38485 ( 9655 hex ) 6 Bytes
Touchscreen Menu Path:
Home → Log → Start Current / Temperature / Overload →
Last Peak Start Current / Last Temperature / Last Overload -7
P16.8 – Event Time –
Last Peak Start Current / Last Temperature / Last Overload -8
Holding
Register Type:
Description:
Read Only
Displays the event time -8.
Range: Modbus Decimal Value: Default:
hh:mm:ss Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
GMT
Modbus Address: Modbus Format:
38488 ( 9658 hex ) 6 Bytes
Touchscreen Menu Path:
Home → Log → Start Current / Temperature / Overload →
Last Peak Start Current / Last Temperature / Last Overload -8