Page 3–62 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails – “log” menu of parameTers (ConTinued)
Each SR55 is tested at the factory, and each unit may have a brief log history from this
testing.
P16.9 – Event Time –
Last Peak Start Current / Last Temperature / Last Overload -9
Holding
Register Type:
Description:
Read Only
Displays the event time -9.
Range: Modbus Decimal Value: Default:
hh:mm:ss Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
GMT
Modbus Address: Modbus Format:
38491 ( 965B hex ) 6 Bytes
Touchscreen Menu Path:
Home → Log → Start Current / Temperature / Overload →
Last Peak Start Current / Last Temperature / Last Overload -9
log “Trip log” & evenT Times parameTers
P17.0 – Last Trip Type:
Description:
Read Only
Displays the last Fault trip.
• Refer to “Trip Code Descriptions” in this chapter.
Range: Modbus Decimal Value: Default:
• Trip: 0 – 65,535
• Trip Time: hh:mm:ss
• linear scale ( 1 = 1 )
• Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
• 0
• GMT
Modbus Address: Modbus Format:
• Trip: 60608 ( ECC0 hex )
• Trip Time: 60672 ( ED00 hex )
• 16-bit unsigned
• 6 Bytes
Touchscreen Menu Path:
Home → Log → Trip Log → Last Trip
P17.1 – Last Trip -1 Type:
Description:
Read Only
Displays the last Fault trip -1.
• Refer to “Trip Code Descriptions” in this chapter.
Range: Modbus Decimal Value: Default:
• Trip: 0 – 65,535
• Trip Time: hh:mm:ss
• linear scale ( 1 = 1 )
• Time (ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
• 0
• GMT
Modbus Address: Modbus Format:
• 60609 ( ECC1 hex )
• 60675 ( ED03 hex )
• 16-bit unsigned
• 6 Bytes
Touchscreen Menu Path:
Home → Log → Trip Log → Last Trip -1