10 Repair and Check
© Copyright Reserved Autonics Co., Ltd. 149
10 Repair and Check
10.1 Change repair component
10.1.1 Battery change
Battery of LP-S070 is available for maintain user-defined setting, data backup of latch area, and
time if there is unexpected power failure or it is not able to supply power. You need to change
battery regularly.
(1) The status with discharged battery
When time is not correct.
After power failure, time is reset.
After power failure, data of latch area is reset.
(2) Battery residual quantity display
You can check battery remaining from [Diagnostics]-[Battery remaining] of system setting
menu in LP-S070. Please replace battery if battery remaining is below 5%.
No.
Function and operation
Displays battery remaining with 0 to 100% as numerical percentage.
Displays battery remaining with bar graph
(3) Special register for battery
Current backup battery error
[F0002C]
Turns ON when battery voltage is below than standard
value
Maintain backup battery error
[F0002D]
If current backup battery error turns ON at once, it
maintains ON status before restarting LP-S070.

Table of Contents