3. A downloaded running AutroVoice miniVES system conguration cannot be opened
The downloaded le from the system, cong.afz can be found in the tab Documents –> Selector –> Workspaces_x.x.x (where x
indicates the version of the software) –> downloadedConguration. To run the downloaded le from the system (* .afz) you need to:
1. Select in the conguration software: File –> Import working area
2. As a standard, the conguration software creates les and saves them under: C:\Users\Documents\Selector\
Workspaces_x.x.x \downloadedConguration. If you have chosen a dierent access path, please choose from it the
appropriate le with the .afz extension and then select option Open.
3. When you select Open option, the system asks for the indication of a new folder in order to copy the imported content
from the system conguration. You should create a new folder, give it any name, select it and choose Select Folder
option. Please note that it is a very important step!
4. Select YES option in the window if you want to open the imported conguration
5. The conguration will be loaded – in the System connection window with the Connect option, the Same conguration
status should be shown. If Dierent conguration status is shown in the window, please select File –> Load –> the
newly created folder while importing the le with the .afz extension. There are conguration.afz les available inthe
location they were created when conguring the system. You have to load those les and then check the status until
it shows the Same conguration status.
4. DFMS, DMS or DMS-LCD microphone reboots when connected to the system
If you additionally connect a microphone to a properly functioning system, and it resets after connection this means that the
microphone does already have a preloaded conguration in it’s internal memory which is dierent from the conguration
of the system. Inthis situation the factory (default) settings should be restored to the microphone and then the microphone
should be reconnected.
5. The conguration software suspends while trying to compare the topology
oftheconguration created in oine mode
If the system cannot properly detect the devices available on the AutroVoice miniVES network and prevents assigning MAC
addresses to the conguration items created in oine mode it means that the list of devices in the Working area is dierent
from what is visible in the system. The solution to this, is to create a new project, which does not include any devices in the work-
space and then select the Recreate topology option (System –> Connection Settings). In this way you get to know the correct
arrangement of the system devices in the workspace.
The arrangement of devices in the workspace should be restored to it’s original conguration created in oine mode and then
option Recreate topology –> Compare should be reselected. Followed by a table appearing with all elements available in the
system. To ll in the missing MAC adresses and serial numbers, use the FIX button.
6. The system does not respond to command Restore to Factory Defaults
Each project possess its own unique Factory Defaults signature, which is available in the window: Basic Conguration –> Factory
Defaults. Every time you call the Default settings, the system checks the validity of the system signature with the one located in
the congurator. Lack of compatibility will cause the command disregard.
7. How should I transfer a conguration that can be opened on another computer?
Full conguration means the device settings, source audio les, and summary of matrix, scenarios, zones etc. after conversion
topcm. It is written via Export workspace function in the File tab.