90
COMPACT VOICE ALARM SYSTEM
SERVICE MANUAL
3
Auto-Save Interval
This option, when activated, results in having the current conguration saved into the conguration le at predened
intervals expressed in minutes.
4
Auto-Save History
In this section you declare the number of autosave congurations you wish to be stored in the software. It is closely linked
to the autosave interval, if the interval is set to 1 minute and the value of the autosave readout is 10, then the congurator
will allow to load the maximum of 10 minutes back. Of course, both the save interval and the number of les to read may
assume a value from 1 to 99.
12.3.3 System
1
Verify Conguration
The congurator checks created conguration for it’s integrity. It classies veried elements into 3 groups – Errors, Warnings
and Info. If the software detects conguration errors, it will not allow it to be loaded into the system. By selecting Showdetails,
we gain access into the details of the problems which have occurred.
2
Restore to factory defaults
This function completely erases conguration les, logs and audio les from all of the devices connected to the AutroVoice
miniVES system. All of the memory cards will be formatted and the devices will be assigned with IP addresses from the
192.18.x.x pool. The packets responsible for the factory settings commands are UDP and are received regardless of the
set internal IP addresses in the system. If the System has executed the restore to factory defaults command, the project
signature has also been changed, in order to update it in the congurator software you must download the system cong-
uration. You can also select the recreate topology option, enter an empty conguration into the system and then restore
the system to factory defaults.