12.2 Basic Conguration
1
Project name and author window, with designer’s note
The Project eld contains basic information on conguration of the AutroVoice miniVES system. The name of the project and
its author should be supplemented here, as well as a description which should include as many detailed data as possible,
such as the place and date launched, specic features of the system, customized functions. The more detailed the project
description the easier servicing and making changes in the system at a later date.
2
Language selection
The Language eld denes the current language of the software used to congure the AutroVoice miniVES system – Selector
Language. System Language denes the current language of all available GUI touch screens in the system.
3
System real-time clock setting
Setting the system valid time. The congurator downloads the UTC from the operating system on which the congurator
is installed. In order to load time together with conguration, accept the Sync UTC in upload window and select the
appropriate time zone in which the system will be installed. It’s possible to turn daylight savings time on and o in this
section. Choose Auto setting DST for the time to be advanced by 1 hour on the last Sunday of March at 1:00 universal time
and retarded accordingly on the last Sunday of October. This applies to countries within the EU among others (UE 2000/84/EC
directive). Inthis mode if the computer running the software is in a daylight savings zone the Selector software will act
accordingly and display DST start and stop dates. It’s possible to manually override the transition dates by using the next
option Manual setting DST along with use DST (without the latter daylight savings time will be disabled). Additionally time
can be updated automatically by a PTP server connected either to the LAN port of the central unit or the LAN/WAN port.
4
Signature
Every project is assigned with a unique signature number. If the signatures between the project uploaded to the system and
the one on the project in the computer software dier, the system will not allow returning to factory settings.
5
Congurator work mode
In Global Settings you can choose one of the congurator’s modes. The Advanced mode, unlike the Simple mode, is able
to create speaker zone groups, logical input / output groups, timers and scenarios. Additionally, in the Advanced mode,
inediting logical outputs, it is possible to set individual diode operation on zone microphones. TheEnableBlackBox option
– enables the reman microphone to record audio while the system is in the alarm mode. TheEnable Loop Control option –
enabling this option turns on reporting of all errors detected in the bre-optic loop.