6-20
■ PV filter setup
The PV filter (primary filter with the software) is activated to remove the noise
from the PV input.
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) Press the [para] key several times.
>> Display the parameter setting [FL: PV filter].
(3) Press the [<], [], or []key to change the set value in
[FL].
Setting range: 0.0 to 120.0s
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>> The display is returned to the operation display.