6-21
PV bias setup
The PV bias is activated to correct the PV input error.
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) Press the [para] key several times.
>> Display the parameter setting [bI: PV bias].
(3) Press the [<], [], or []key to change the set value in
[bI].
Setting range: -1999 to + 9999U
The decimal point position is changed corresponding to the PV range.
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>> The display is returned to the operation display.
<
<
Chapter 6. SETTINGS DURING OPERATION
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp