7-4
Chapter 7. LIST OF SIMPLE CONFIGURATION DISPLAY ITEMS
Display Item Contents
Initial value
Notes
Time proportional 5 to 120s (when the output includes 10 Displayed when the heat/cool control
cycle time 2 (cool) the relay output) or is used.
1 to 120s (when the output does not 2
When the output destination of the tim
include the relay output)
proportional output 2 includes the relay
output, the relay output is operated with
time proportional cycle time of 5 sec. even
though a value less than 5 sec. is set.
AT type 1 Displayed when the control method is
other than ON/OFF control (CtrL 0).
0: Normal (Standard control
characteristics)
1: Immediate response (Control
characteristics immediately responding
to the external disturbance.)
2: Stable (Control characteristics with
less up/down fluctuation of PV)