Display Item Contents
Initial value
Notes
Operation type of 0: No event 0
internal event 1 1: PV high limit
2: PV low limit
3: PV high/low limit
4: Deviation high limit
5: Deviation low limit
6: Deviation high/low limit
7: Deviation high limit 
(Final SP reference)
8: Deviation low limit 
(Final SP reference)
9: Deviation high/low limit 
(Final SP reference)
10: SP high limit
11: SP low limit
12: SP high/low limit
13: MV high limit
14: MV low limit
15: MV high/low limit
16: CT1 heater burnout/over-current
17: CT1 heater short-circuit
18: CT2 heater burnout/over-current
19: CT2 heater short-circuit
20: Loop diagnosis 1
21: Loop diagnosis 2
22: Loop diagnosis 3
23: Alarm (status)
24: READY (status)
25: MANUAL (status)
26: Invalid
27: During AT execution (status)
28: During SP ramp (status)
29: Control direct action (status)
30: During ST execution (status)
31: Invalid
32: Timer (status)
33: High and low limits of MFB value
(Invalid in this unit)
Internal event 1 As described below. 0000
1st digit: Direct/ 0: Direct 0
Reverse 1: Reverse
2nd digit: Standby 0: None 0
1: Standby
2: Standby + Standby at SP change
3rd digit: Operation 0: Continue 0
at READY 1: Forced OFF
4th digit: Undefined 0 0
7-8
Chapter 7. LIST OF SIMPLE CONFIGURATION DISPLAY ITEMS
Handling Precautions
• If ROM version 1 of the instrument information bank (Id02) is prior to
2.04, “33” cannot be set as [Internal Event configuration 1 operation
type].