4-6
5-wire system
Do not connect any terminating resistor to both ends of the
communication path. Doing so might cause the communication to
fail.
Even though any units requiring the terminating resistor exist in the
communication path, do not connect any terminating resistor.
Handling Precautions
Do not connect DA and DB. Doing so might cause damage to this
unit.
Ground the shield line to one point on one side of the cable.
Be sure to connect SG terminals each other.
Failure to do so might cause unstable communications.
Chapter 4. WIRING
16
17
18
16
Master station
DA
DA
DB
DB
SG
SG
SG
FG
+
-
+
-
This unit (slave station)
This unit (slave station)
Shield
Shield
17
18
Important