5-4
■ Temperature unit setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key.
>> The setup setting [C02: Temperature unit] is
displayed.
(4) Press the [<], [], or []key to set the value you have
selected from the following in [C02].
0: Centigrade (°C)
1: Fahrenheit (°F)
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
When the input type of the model is "T: Thermocouple" or "R: RTD",
[C02: Temperature unit] can be displayed. However, when the input
type is "L: DC current or DC voltage", [C02] cannot be displayed.