5-19
■ Event operation type setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [E1.C1: Internal Event 1
operation type].
(4) Press the [<], [], or []key to change the set value
in [E1.C1].
Setting range: 0 to 33
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
• The displays of internal event 2 to 5 operation types are [E2.C1],
[E3.C1], [E4. C1], and [E5.C1].
• Five internal events 1 to 5 are provided. However, the number of
event outputs determined by the optional function is 0 to 3 points. In
"Simple configuration", the operation of internal events 1 to 3 are
output to event outputs 1 to 3. To use the operation of the internal
events 4 to 5, the setup mode is changed to "High function
configuration", and then [DO assignment] must be set.