5-22
Event sub-setting setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) Press the [para] key several times.
>> Display the parameter setting [E1.Sb: Internal Event
1 sub-setting].
(3) Press the [<], [], or []key to change the set value
in [E1.Sb].
Setting range: -1999 to +9999
The decimal point position is changed corresponding to the event operation
type.
For a part of the event operation types, the setting range becomes 0 to + 9999.
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
The displays of the internal event 2 to 5 sub-settings are [E2.Sb],
[E3.Sb], [E4.Sb], and [E5.Sb].
When the internal event operation type is [0: No event] or the
operation type does not need sub-setting, the internal event sub-
setting is not displayed.
<
<
Chapter 5. SETTINGS BEFORE STARTING OPERATION
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp

Other manuals for Azbil SDC15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil SDC15 and is the answer not in the manual?

Azbil SDC15 Specifications

General IconGeneral
BrandAzbil
ModelSDC15
CategoryController
LanguageEnglish

Related product manuals