5-23
■ Event hysteresis setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) Press the [para] key several times.
>> Display the parameter setting [E1.Hy: Internal Event
1 hysteresis].
(3) Press the [<], [], or []key to change the set value
in [E1.Hy].
Setting range: 0 to 9999
The decimal point position is changed corresponding to the event operation
type.
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
• The displays of the internal event 2 to 5 hysteresis are [E2.Hy],
[E3.Hy], [E4.Hy], and [E5.Hy].
• When the internal event operation type is [0: No event] or the
operation type does not need hysteresis, the internal event hysteresis
is not displayed.