Chapter 5. SETTINGS BEFORE STARTING OPERATION
■ CT output setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) n the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C37: CT1 output].
(4) Press the [<], [], or []key to set the value you have
selected from the following in [C37].
0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3
Set an output used for ON/OFF control of the heater power, on which CT
(current transformer) is installed.
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
• The display of the CT2 output is [C40].
• When the optional function of the model is that CT is not provided,
[C37] and [C40] are not displayed.
When [C36] is set at [1: Current measurement], [C37] is not
displayed.
When [C39] is set at [1: Current measurement], [C40] is not
displayed.