5-26
Chapter 5. SETTINGS BEFORE STARTING OPERATION
■ CT wait time before measurement setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C38: CT1 wait time before
measurement].
(4) Press the [<], [], or []key to change the set value
in [C38].
Setting range: 30 to 300ms
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
• The display of [CT2 wait time before measurement] is [C41].
• When the optional function of the model is that CT is not provided,
[C38] and [C41] are not displayed.
When [C36] is set at [1: Current measurement], [C38] is not
displayed.
When [C39] is set at [1: Current measurement], [C41] is not
displayed.