5-32
Chapter 5. SETTINGS BEFORE STARTING OPERATION
■ Station address setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C65: Station address].
(4) Press the [<], [], or []key to change the set value
in [C65].
Setting range: 0 to 127
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
• Set [Station address] of an instrument multidrop-connected through
the RS-485 to a value other than “0”, which is not duplicated. If
[Station address] is set at “0”, the communication cannot be
performed.
• When the optional function of the model includes RS-485, [C65] is
displayed.