5-32
Chapter 5. SETTINGS BEFORE STARTING OPERATION
Station address setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C65: Station address].
(4) Press the [<], [], or []key to change the set value
in [C65].
Setting range: 0 to 127
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
Set [Station address] of an instrument multidrop-connected through
the RS-485 to a value other than “0”, which is not duplicated. If
[Station address] is set at “0”, the communication cannot be
performed.
When the optional function of the model includes RS-485, [C65] is
displayed.
<
<
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp