6-15
rE-1 (Manual reset) setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) Press the [para] key several times.
>> Display the parameter setting [rE-1: Manual reset].
(3) Press the [], or []key to change the set value in
[rE-1].
Setting range: -10.0 to +110.0%
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
When [CtrL: Control method] is set at [0: ON/OFF control], [rE-1] is
not displayed.
When [C26: Heat/Cool control selection] is set at [0: disabled] and [I-
1: Integral time] is set at a value other than “0”, [rE-1] is not displayed.
When [C26: Heat/Cool control selection] is set at [1: enabled] and
both [I-1: Integral time] and [I-1c: I (integral time) (cool)] are set at a
value other than “0”, [rE-1] is not displayed.
<
<
Chapter 6. SETTINGS DURING OPERATION
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp