2-34
Chapter 2.  PARA BANK SETTINGS 
Display Auxiliary 
display
Item Settings and descriptions Initial 
value
User 
setting
Remarks
TYPE F06.
Mathematical/logical operations 
Same as for F01. 0 Same as for F01.
PA-0 1 F06.
Setting 1  0.0
PA-02 F06.
Setting 2  0.0
PA-03 F06.
Setting 3  0
DI .SEL F06.
Contact input  1024
DI F06.
Contact input monitor  -
DO F06.
Contact output monitor  -
OUT F06.
Computation unit output 
check point value
-
TYPE F07.
Mathematical/logical operations 
0: NOP  No operation 
1: FLT  First-order lag filter 
2: R/B  Ratio/bias
3: HLL  High/low limiter
4: DRL  Change rate limiter
5: LED  Differentiation
6: L/L  Advance/delay
7: ABS  Absolute value
8: TBL  Linearization table
9: MAX  Maximum value hold
10: MIN  Minimum value hold
11: HLD  Hold
12: PRS  Preset value
13: SPR  Soft preset value
14 to 30: No operation
31: ADD  Addition/subtraction
32: MUL  Multiplication
33: DIV  Division
34: HSE  High selector
35: LSE  Low selector
36: SWS  Switch selector
37: CPS  Change point selector
38: SSS  Soft switching selector
0 14 to 38 can be set with compu-
tation unit 07 only.
PA-0 1 F07.
Setting 1  -19999 to +32000 U 0.0 The decimal point position is 
determined by the setting for 
the decimal point position in 
the input computation bank.
PA-02 F07.
Setting 2  0.0
PA-03 F07.
Setting 3  0 to 255 0
DI .SEL F07.
Contact input  1024 to 2047 1024 For more details on the 1024 to 
2047 range, see the Standard 
bit codes (P.4-1).
DI F07.
Contact input monitor  0: OFF  1: ON -
DO F07.
Contact output monitor  -
OUT F07.
Computation unit output 
check point value
-19999 to +32000 U - The decimal point position is 
determined by the setting for 
the decimal point position in 
the input computation bank.
TYPE F08.
Mathematical/logical operations 
Same as for F01. 0 Same as for F01.
PA-0 1 F08.
Setting 1  0.0
PA-02 F08.
Setting 2  0.0
PA-03 F08.
Setting 3  0
DI .SEL F08.
Contact input  1024
DI F08.
Contact input monitor  -
DO F08.
Contact output monitor  -
OUT F08.
Computation unit output 
check point value
-
TYPE F09.
Mathematical/logical operations 
Same as for F01. 0 Same as for F01.
PA-0 1 F09.
Setting 1  0.0
PA-02 F09.
Setting 2  0.0
PA-03 F09.
Setting 3  0
DI .SEL F09.
Contact input  1024
DI F09.
Contact input monitor  -
DO F09.
Contact output monitor  -
OUT F09.
Computation unit output 
check point value
-
TYPE F 10.
Mathematical/logical operations 
Same as for F01. 0 Same as for F01.
PA-0 1 F 10.
Setting 1  0.0
PA-02 F 10.
Setting 2  0.0
PA-03 F 10.
Setting 3  0
DI .SEL F 10.
Contact input  1024
DI F 10.
Contact input monitor  -
DO F 10.
Contact output monitor  -
OUT F 10.
Computation unit output 
check point value
-