22 english
10
Resetting all values (reset)
NOTICE!
Interference in function
Resetting the values while the system is running may
result in malfunctions.
Stop the system before performing the reset.
The reset function can be used to restore all the settings
to the factory settings. For a reset the magnet may also
be located outside the measuring range.
LED display Displayed values (example)
LED1 LED2 At 0 to 10 V At 4 to 20 mA
5.39 V 10.80 mA
1. Activate buttons
Hold down any button for at least 3s.
> 3 s
2
1
5.39 V 10.80 mA
Release button.
< 1 s
Within 1s, hold down
and
simultaneously
for at least 3s.
> 3 s
1
2
Output indicates error value.
10.50 V 3.60 mA
Buttons are activated.
If an error or an interruption occurs while
activating the buttons, allow a wait time of 12s
before retrying.
2. Reset
Hold down
and
for at least 6s.
> 6s
1
2
Output indicates zero value.
0.00V 4.00 mA
All values are reset.
Release buttons.
Current position value is displayed.
Buttons are locked.
8.43 V 15.67 mA
LED legend: LED not on
LED green LED flashing green
LED 1 and LED 2 flashing green-red simultane-
ously
BTL7-A/C/E/G_ _ _-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S135/S140/KA_ _/FA_ _
Micropulse Transducer - Rod Style