92 P/N 133487
Banner Engineering Corp. Minneapolis, U.S.A.
www.bannerengineering.com Tel: 763.544.3164
SC22-3 Safety Controller
Instruction Manual
Appendix A
A.9.2 SC22-3 Enabling Device Hookup Options
The device is shown in the actuated position or Stop state.
Dual-Channel (2 terminals or 3 terminals): This circuit typically
can meet ISO 13849-1 Category 2 or 3 requirements depending
on the safety rating and installation of the enabling device(s).
Dual-channel 3-terminal hookup uses pulse monitoring and can
detect a short circuit to another source of power. Both 2- and 3-
terminal hookups can detect a short between channels when the
contacts are open if the short is present longer than 2 seconds.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
Dual-Channel (PNP device): This circuit can meet ISO 13849-1
Category 2, 3, or 4 requirements depending on the safety rating,
installation, and the fault detection (e.g., short circuit) capabilities
of the enabling device. The SC22-3 does not provide short circuit
detection in this configuration.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
Dual-Channel (4 terminals): This circuit can meet ISO 13849-1
Category 2, 3, or 4 requirements, depending on the safety rating
and the installation of the enabling device. This circuit can detect
a short circuit between channels or to another source of power.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
Complementary (2 terminals or 3 terminals): This circuit can
meet ISO 13849-1 category 2, 3, or 4 requirements depending
on the safety rating and the installation of the output device.
This circuit can detect a short circuit between channels. In the
actuated condition (e.g., S1 open/S2 closed) a short across the
closed contact can cause the response time to increase based
on the debounce time. In this situation, the response time could
be longer as specified, based on the (selected) debounce time,
see Section 3.2.2.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
S1 S2
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
S1 S2
Complementary (PNP device): This circuit can meet
ISO 13849-1 category 2, 3, or 4 requirements depending on the
safety rating and the installation of the output device. This circuit
can detect a short circuit between channels. In the actuated
condition (e.g., S1 OFF/S2 ON) a short across the closed
contact can cause the response time to increase based on the
debounce time. In this situation, the response time could be
longer as specified, based on the (selected) debounce time, see
Section 3.2.2.
Two-Hand Operation
2-Ch, 2 Terminals 2-Ch, 2 Terminals2-Ch, 3 Terminals 2-Ch, 4 Terminals
2-Ch, 2 Terminals
2 PNP
Two Hand Operation - 2x Dual Channel Complementary
2x Complementary,
4 Terminals
2x Complementary,
5 Terminals
2x Complementary,
4 Terminals, 4 PNP
Revision History
Rev C - Corrected OFF” and ON” on Two-hand Operation - 2x Dual Channel Complementary, 2x Complementary, 4 Terminals, 4 PNP
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
13-Oct-06 Rev. E Gray lines moved below the black lines
21-Nov-06 Rev. F - Added + sign to 2-Ch, 3 Terminals, 2-Ch, 4 Terminals, 2x Dual Channel Complementary, 5 Terminals
10-Jan-07 Rev. G - Changed + sign text to outlines, changed gray lines to 6 pt. dashed lines
25-May-07 Rev H - Changed 2-Ch, 2 Terminals 2 PNP; 2x Complementary, 5 Terminals (centered arrow) and 2x Complementary, 4 Terminals, 4 PNP
20-Sept-07 Rev I - Added another 2-ch, 2 Terminal for the manual
24V
24V
OFFOFF
ONOFF ONOFF
24V
S1 S2
2x Complementary (4 terminals or 5 terminals): This circuit
can meet ISO 13849-1 category 3 or category 4 requirements
depending on the design and installation of the enabling device.
This circuit can detect a short circuit between channels. In the
guard closed condition (e.g., S1 open/S2 closed) a short across
the closed contact can cause the response time to increase
based on the debounce time. In this situation, the response
time could be longer than specified, based on the (selected)
debounce time, see Section 3.2.2.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
S1 S2
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
2x Complementary (PNP device): This circuit can meet ISO
13849-1 category3 or category 4 requirements depending on the
design and installation of the enabling device. This circuit can
detect a short circuit between channels. In the actuated condition
(e.g., S1 OFF/S2 ON) a short across the closed contact can
cause the response time to increase based on the debounce
time. In this situation, the response time could be longer than
specified, based on the (selected) debounce time, see Section
3.2.2.
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals 2-Ch, 3 Terminals 2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFFOFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ONOFF
2x Complementary,
4 Terminals, 2 PNP
ONOFF ONOFF
S1 S2

Table of Contents

Other manuals for Banner SC22-3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Banner SC22-3 and is the answer not in the manual?

Banner SC22-3 Specifications

General IconGeneral
BrandBanner
ModelSC22-3
CategoryController
LanguageEnglish

Related product manuals