Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
54
of 208
4.3
P0817
You can read the operation source by this parameter.
P0818
Only after an over-current OC or over-voltage OV fault occurs, the b maXX
®
1000 can be
reset/restarted automatically up to 10 times.
Setting this parameter to 0 will disable automatic reset/restart operation after any fault has
occurred.
When enabled, the b maXX
®
1000 will restart with speed search, which starts at the fre-
quency before the fault. To set the waiting time before restart after a fault, please set base
block time for speed search ZP0897–.
P0819
This parameter should be used in conjunction with ZP0818–.
For example:
If ZP0818– is set to 10 and ZP0819– is set to 600 s (10 min), and if there is no fault for
over 600 seconds from the restart for the previous fault, the auto reset times for restart
after fault will be reset to 10.
P0817
Anzeige der Sollwertquelle 0 to 63
- Display the operation command source 32
A BM_u_DisplayOpCommandSource 1:1 -
Display value Bit Meaning
1 Bit 0 1: Operation command source by digital keypad
2 Bit 1 1: Operation command source by ProDrive communication
4 Bit 2 1: Operation command source by external terminal 2/ 3 wire mode
8 Bit 3 1: Operation command source by multi-function input
16 Bit 4 Reserved
32 Bit 5 1: Operation command source by CANopen
P0818
Wiederanlauf bei Fehler 0 to 10
EE Auto restart after (OC or OV) fault numbers 0
STOP BM_u_AutoOCOVRestart 1:1 -
P0819
Zeit bis zum Zurücksetzen der Anzahl nach Wie-
deranlauf bei Fehler
0.1 to 6000.0 s
EE Auto reset time at restart after fault 60.0 s
STOP BM_u_AutoResetTime 10:1 -