Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
86
of 208
4.3
P1105
The external multi-function input terminals are falling-edge triggered. For standard b
maXX
®
1000 (without extension card), there are MI1 to MI6 and ZP1105– will display 63
(111111) for no action.
Figure 33: Display status multi function input terminal 1
For Example:
If ZP1105– displays 52, it means MI1, MI2 and MI4 are active.
The display value
52 = 32 + 16 + 4 = 1 x 2
5
+ 1 x 2
4
+ 1 x 2
2
= bit 6 x 2
5
+ bit 5 x 2
4
+ bit 3 x 2
2
Figure 34: Display status external multi function input terminal 2
P1105
Statusanzeige externe Multi-Funktions-Eingänge 0 to 4095
- Display the status of external multi function
input terminals
0
A BM_u_StatusExtMulitFunctionInputTerminals 1:1