Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
156
of 208
A
P0061 Motor nominal frequency 0.10 to 600.00 Hz 50.00 Hz (ZP0310– = 9)
or
60.00 Hz (ZP0310– = 10)
100:1 28
P0065 Motor number of pole pairs 1 to 10 2 1:1 28
P0077 Motor line-to-line resistance 0 to 65535 mΩ abc 0 mΩ abc 1:1abc 29
P0110 Motor no-load current 0.0 to 99.0 %
ZP0054–
40.0 % ZP0054– 10:1 29
P0111 Motor rated slip (Motor nominal slip) 0.00 to 20.00 Hz 3.00 Hz 100:1 29
P0112 Torque compensation 0.0 to 10.0 Hz 0.0 Hz 10:1 29
P0113 Torque compensation time constant 0.01 to 10.00 s 0.10 s 100:1 30
P0114 Motor slip compensation 0.00 to 10.00 % 0.00 % 1:1 30
P0115 Motor slip compensation limit 0 to 250 % 200 % 1:1 30
P0116 Motor slip compensation time constant 0.05 to 10.00 s 0.20 s 100:1 s 31
P0117 Motor PTC overheat protection 0 to 1 0 1:1 31
P0118 Input filter time constant of the PTC protection 0 to 9999 100 (200 ms) 1:2 31
P0119 Motor PTC overheat fault level 0.1 to 10.0 V 2.4 V 10:1 32
P0120 Motor PTC overheat warning level 0.1 to 10.0 V 1.2 V 10:1 33
P0121 Motor PTC overheat reset delta level 0.1 to 5.0 V 0.6 V 10:1 33
P0122 Motor PTC overheat warning protection 0
to 2 0 1:1 34
P0123 Motor rated speed/nominal slip master selection 0
to 1 1 1:1 34
P0124 Motor rated speed/nominal slip master selection con-
firm
0
to 2 0 1:1 34
P0240 Present fault record 0 to 052F
hex
0 1:1 35
P0241 Second most recent fault record 0 to 052F
hex
0 1:1 36
P0242 Third most recent fault record 0 to 052F
hex
0 1:1 37
P0243 Fourth most recent fault record 0 to 052F
hex
0 1:1 37
P0244 Fifth most recent fault record 0 to 052F
hex
0 1:1 37
P0296 Reaction CAN-bus drop-out 0 to 255 0 1:1 38
P0297 Error reaction power lost 0 to 255 0 1:1 38
P0300 Controlword 0
hex
to FFFF
hex
0 1:1 39
P0301 Statusword 0 to 65535 0 1:1 40
P0304 Operation mode actual 0 to 249 249 1:1 42
P0305 Drive status 0 to 15 0 1:1 42
P0310 Parameter reset 0 to 11 0 1:1 43
P0311 Data set status 0 to 2 0
1:1
43
P0317 EEPROM write count 1 to 65535 0 1:1 43
P0558 Controller hardware version 0 to 65535 1 1:1 44
P0800 Control method 0 to 1 0 1:1 44
P0801 Source of first master frequency command 1 to 225 5 1:1 44
P0802 Source of first operation command 1 to 5 5 1:1 45
P0803 Stop method 0 to 3 1 1:1 46
P0805 Line start lockout 0 to 3 1 1:1 48
P0806 Loss of ACI Signal 0 to 2 1 1:1 50
P0807 Up/Down Mode 0 to 3 0 1:1 51
P0809 Source of second master frequency command 1 to 255 0 1:1 51
Parameter Range Standard value Internal
standard-
ization
Page