Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
43
of 208
4
P0310
This parameter allows the user to reset all parameters to the factory settings except the
fault records (ZP0240– to ZP0244–).
50 Hz:
ZP0033– and ZP0061– are set to 50 Hz and ZP0053– will be set by ZP0032–
60 Hz:
ZP0033– and ZP0061– are set to 60 Hz and ZP0053– will be set to 230 V or 460 V
When ZP0310–= 11, all parameters are read-only.
To write all parameter, set ZP0310–= 0
P0311
This parameter displays the status of the last data set management command.
P0317
Number of write counts in EEPROM. This counter will be incremented at write access for
parameters (ZP0077–, ZP0110–, ZP0811–, ZP0812–, ZP0850–, ZP1172–, ZP1173–
, ZP1176–, ZP1177–, ZP1180–, ZP1181–, ZP1182–, ZP1183–, ZP1184–, ZP1359–
, ZP1361–, ZP1362–, ZP1363–, internal parameter 1, internal parameter 2) to EE-
PROM by Power OFF.
P0310
Parameter Reset 0 to 11
EE Parameter reset 0
STOP BM_u_ParameterReset 1:1 -
Value Meaning
0 Parameter can be set and read
3 to 8 Reserved
9 Reset parameter to factory setting for 50 Hz motor
10 Reset parameter to factory setting for 60 Hz motor
11 Parameter are read only
P0311
Datensatzverwaltung Status 0 to 2
- Data set status 0
A BM_w_RecordStatus 1:1 -
Status Meaning
0 No error
1 Write/read cycle in process
2 Error
P0317
Anzahl Schreibvorgänge EEPROM 1 to 65535
- EEPROM write count 0
A BM_u_EepromWriteCount 1:1 -