Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
115
of 208
4
P1180
The ramp-up time is used to determine the time required for the b maXX
®
1000 to ramp
from 0 Hz to maximum output frequency ZP0033–. The rate is linear unless S-curve is
„Enabled“; see ZP1177–.
Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals
(MI3 to MI5 or MI7 to MI12) ZP1091– to ZP1093– or ZP1095– to ZP1100– to 7.
Standardization see ZP1186–.
P1181
The ramp-down time is used to determine the time required for the b maXX
®
1000 to de-
celerate from the maximum output frequency ZP0033– down to 0 Hz. The rate is linear
unless S-curve is „Enabled.“, see ZP1177–.
Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals
(MI3 to MI5 or MI7 to MI12) ZP1091– to ZP1093– or ZP1095– to ZP1100– to 7.
Standardization see ZP1186–.
P1182
The jog ramp-up time is used to determine the time required for the b maXX
®
1000 to
ramp from 0 Hz to maximum output frequency ZP0033–. Standardization see ZP1186–
for further information refer to ZP1184–.
P1183
The jog ramp-down time is used to determine the time required for the b maXX
®
1000 to
decelerate from the maximum output frequency ZP0033– down to 0 Hz. Standardization
see ZP1186– for further information refer to ZP1184–.
P1180
HLG Hochlaufzeit 2 0.1 to 600.0 s or
0.01 to 60.00 s
EE RFG ramp-up time 2 10.0 s
ON BM_u_RFG1RampUpTime2 10:1 or 100:1
P1181
HLG Rücklaufzeit 2 0.1 to 600.0 s or
0.01 to 60.00 s
EE RFG ramp-down time 2 10.0 s
ON BM_u_RFG1RampDownTime 2 10:1 or 100:1
P1182
HLG Tippbetrieb Hochlaufzeit 0.1 to 600.0 s or
0.01 to 60.00 s
EE RFG jog ramp-up time 10.0 s
ON BM_u_RFGJogRampUpTime 10:1 or 100:1
P1183
HLG Tippbetrieb Rücklaufzeit 0.1 to 600.0 s or
0.01 to 60.00 s
EE RFG jog ramp-down time 10.0 s
ON BM_u_RFGJogRampDownTime 10:1 or 100:1