Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
84
of 208
4.3
P1103
This parameter can be used to set the status of multi-function terminals (MI1 to MI6 (N.O./
N.C.) for standard b maXX
®
1000).
Figure 31: Multi function input contact selection 1
The MI1 to MI3 setting will be invalid when the operation command source is external ter-
minal (2/3wire).
The setting method: It needs to convert binary number (6-bit) to decimal number for input.
For example:
If setting MI3, MI5, MI6 to be N.C. and MI1, MI2, MI4 to be N.O. The setting value
ZP1103– should be
bit5 x 2
5
+ bit4 x 2
4
+ bit2 x 2
2
= 1 x 2
5
+ 1 x 2
4
+ 1 x 2
2
= 32 + 16 + 4 = 52
as shown in the following.
Figure 32: Multi function input contact selection 2
P1103
Externer Multi-Funktions-Eingang 0 to 4095
EE External multi function input contact selection 0
STOP BM_u_ExtMultiFunctionInputContactSel 1:1