Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
76
of 208
4.3
Figure 22: Position of the control terminals
P1091
Settings for the multi function input terminals.
P1091
Multi-Funktions-Eingang (MI3) 0 to 24
EE Multi function input terminal (MI3) 1
STOP BM_u_MultiFunctionInputTerminalMI3 1:1 -
Value Function Description
0 No function Any unused terminals should be programmed to 0 to insure
they have no effect on operation.
1 Multi step speed command 1 These four inputs select the multi speed defined via ZP1189–
to ZP1203–as shown in ZFigure 23– on page 78.
NOTE:
There are 17 step speed frequencies (including master fre-
quency and jog frequency) to select for application.
2 Multi step speed command 2
3 Multi step speed command 3
4 Multi step speed command 4
5 External reset The external reset has the same function as the reset key on
the digital keypad. After faults such as 0003
hex
, 0500
hex
and
051B
hex
are cleared this input can be used to reset the drive.
6 Accel/decel inhibit When the command is active, acceleration and deceleration is
stopped and the b maXX ® 1000 maintains a constant speed.
7 Accel/decel time selection
command
Used to select the one of 2 Accel/Decel times (ZP1172–,
ZP1173– and ZP1180–, ZP1181–). See explanation at the
end of this table.
8 Jog operation control Parameter value 8 programs one of the multi function input ter-
minals MI3 to MI5 (ZP1091– to ZP1093–) for jog control.
NOTE:
Programming for jog operation by 8 can only be done while the
motor is stopped. (Refer to parameter ZP1182– to ZP1184–)
9 External base block
(ZP0896–)
Parameter value 9 programs a multi function input terminals for
external base block control.
NOTE:
When a base-block signal is received, the b maXX ® 1000 will
block all output and the motor will free run. When base block
control is deactivated, the b maXX ® 1000 will start its speed
search function and synchronize with the motor speed, and
then accelerate to master frequency.