Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
64
of 208
4.3
P0895
If the duration of a power loss is less than this parameter setting, the b maXX
®
1000 will
resume operation. If it exceeds the maximum allowable power loss time, the b maXX
®
1000 output is then turned off (coast stop).
The selected operation after power loss in ZP0894 is only executed when the maximum
allowable power loss time is 5 seconds and the b maXX
®
1000 displays „Lu“.
But if the b maXX
®
1000 is powered off due to overload, even if the maximum allowable
power loss time is 5 seconds, the operation mode as set in ZP0894 is not executed. In
that case it starts up normally.
P0896
This parameter determines the b maXX
®
1000 restart method after external base block
is enabled.
P0895
Maximal erlaubte Spannungsausfallzeit 0.1 to 5.0 s
EE Maximum allowable power loss time 2.0 s
STOP BM_u_DCBrakingDuringStop 10:1 -
P0896
Basis Drehzahlsuche 0 to 2
EE Base-block speed search 1
STOP BM_u_BaseBlockSpeedSearch 1:1 -
Value Meaning
0 Disable speed search
1 Speed search starts with last frequency command
2 Speed search starts with minimum output frequency ZP0038