Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
24
of 208
4.3
P0036
This parameter sets the mid-point frequency of the V/f curve if ZP0800– = 0.
With this setting, the V/f ratio between minimum frequency and mid-point frequency can
be determined. This parameter must be equal to or greater than minimum output frequen-
cy ZP0038– and equal to or less than maximum voltage frequency ZP0061–. This set-
ting is invalid in vector control mode ZP0800– = 1.
The settings have to meet the condition of ZP0038–
≤ ZP0036– ≤ ZP0061–.
Also see ZFigure 8– on page 26.
P0037
This parameter sets the mid-point voltage of any V/f curve if ZP0800– = 0.
The maximum value depends on the b maXX
®
used, up to 255.0 V for single-phase de-
vices and up to 510.0 V for three-phase devices.
With this setting, the V/f ratio between minimum frequency and mid point frequency can
be determined. This parameter must be equal to or greater than minimum output voltage
ZP0039– and equal to or less than maximum output voltage ZP0053–. This setting is
invalid in vector control mode ZP0800– = 1.
The settings have to meet the condition of ZP0039–
≤ ZP0037– ≤ ZP0053–.
Also see ZFigure 8– on page 26.
P0038
This parameter sets the minimum output frequency of the drive if ZP0800– = 0.
This parameter must be equal or less than mid-point frequency ZP0036–. This setting is
invalid in vector control mode ZP0800– = 1.
The settings have to meet the condition of ZP0038–
≤ ZP0036– ≤ ZP0061–.
Also see ZFigure 8– on page 26.
P0036
Mittelfrequenz Fmid 0.10 to 600.0 Hz
EE Mid-point frequency (Fmid) 1.50 Hz
STOP BM_u_MidPointFreq 100:1 Hz -
P0037
Mittelspannung Vmid 0.1 to 255.0 V or
0.1 to 510.0 V
EE Mid-point voltage (Vmid) 10.0 V or 20.0 V
STOP BM_u_MidPointVolt 10:1 V -
P0038
Minimale Ausgangsfrequenz Fmin 0.10 to 600.0 Hz
EE Minimum output frequency (Fmin) 1.50 Hz
STOP BM_u_MinOutFreq 100:1 -