Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
25
of 208
4
P0039
This parameter sets the minimum output voltage of any V/f curve if ZP0800 = 0.
The maximum value depends on the b maXX
®
used, up to 255.0 V for single-phase de-
vices and up to 510.0 V for three-phase devices.
This parameter must be equal to or less than mid-point voltage ZP0037. This setting is
invalid in vector control mode ZP0800 = 1.
The settings have to meet the condition of ZP0039
ZP0037 ZP0053.
Also see ZFigure 8on page 26.
P0040
This parameter must be equal to or greater than the output frequency lower limit
ZP0041.
The maximum output frequency ZP0033 is regarded to 100 %.
Output frequency upper limit value = (ZP0033 ZP0040) / 100
Also see ZFigure 8on page 26.
P0039
Minimale Ausgangsspannung Vmin 0.1 to 255.0 V or 0.1
to 510.0 V
EE Minimum output voltage (Vmin) 10.0 V or 20.0 V
STOP BM_u_MinOutVolt 10:1 V -
P0040
Ausgangsfrequenz: obere Grenze 0.1 to 120.0 %
EE Output frequency: upper limit 110.0 %
STOP BM_u_OutFreqUpperLimit 10:1 -