Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
23
of 208
4
P0010
Display of power unit rate current.
P0024
This parameter determines the operation mode of the cooling fan.
P0032
This parameter determines the base voltage for 50 Hz power supply.
P0033
This parameter determines the b maXX
®
1000 maximum output frequency. All the drive
command sources (analog inputs 0 to +10 V and 4 to 20 mA) are scaled to correspond to
this output frequency range.
Also see ZFigure 8on page 26.
P0010
Leistungsteil Nennstrom 0.0 to 99.9 A
- Power unit rate current 0.0 A
A BM_u_AmpNomCurrent 10:1 -
P0024
Lüfterregelung 0 to 3
EE Fan control 0
ON BM_u_FanControl 1:1 -
Value Meaning
0 Always fan on
1 Fan off after 1 min drive stop
2 Fan on when drive run
Fan off when drive stop
3 Fan on when preliminary temperature attained
P0032
50 Hz Spannungsauswahl 0 to 1
EE 50 Hz base volt selection 0
STOP BM_u_BaseVoltSelect 1:1 -
Value Meaning
0 230V / 400V
1 220V / 380V
P0033
Maximale Ausgangsfrequenz 50.00 to 600.00 Hz
EE Maximum output frequency 50.00 Hz
STOP BM_u_MaxOutputFreq 100:1 -