Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
77
of 208
4
10 UP: Increase master fre-
quency
Increase/decrease the master frequency each time an input is
received or continuously when the input stays active. When
both inputs are active at the same time, the master frequency
increase/decrease is halted. Please refer to ZP0807–. This
function is also called „motor potentiometer“.
11 DOWN: Decrease master fre-
quency
12 Counter trigger Parameter value 12 programs one of the multi function input
terminals MI3 to MI5 (ZP1091– to ZP1093–) to increment the
b maXX ® 1000 internal counter. When an input is received,
the counter is incremented by 1.
13 Counter reset When active, the counter is reset and inhibited. To enable
counting the input should be OFF. Refer to ZP1118– and
ZP1119–.
14 External fault Parameter value 14 programs one of the multi function input
terminals MI3 to MI5 (ZP1091– to ZP1093–) or MI7 to MI11
(ZP1095– to ZP1100–) to be external fault (E.F.) inputs.
15 PID function disabled When an input ON with this setting is ON, the PID function will
be disabled.
16 Output shutoff stop b maXX ® 1000 will stop output and the motor free run if one of
these settings is enabled. If the status of terminal is changed, b
maXX ® 1000 will restart from 0 Hz.
17 Parameter lock enable When this setting is enabled, all parameters will be locked and
write parameters is disabled.
18 Operation command selec-
tion (ZP0802– setting/exter-
nal terminals)
ON:
Operation command via ext. terminals
OFF:
Operation command via ZP0802– setting
ZP0802– is disabled if this parameter value 18 is set. See the
explanation below this table.
19 Operation command selec-
tion (ZP0802– setting/digital
keypad)
ON:
Operation command via digital keypad
OFF:
Operation command via ZP0802– setting
ZP0802– is disabled if this parameter value 19 is set. See the
explanation below this table.
20 Operation command selec-
tion (ZP0802– setting/com-
munication)
ON:
Operation command via communication
OFF:
Operation command via ZP0802– setting
ZP0802– is disabled if this parameter value 20 is set. See the
explanation below this table.
21 Forward/reverse This function has top priority to set the direction for running (if
ZP0805– = 0).
22 Source of second frequency
command enabled
Used to select the first/second frequency command source.
Refer to ZP0801– and ZP0809–.
ON: 2nd Frequency command source
OFF: 1st Frequency command source
23 Quickstop motor control (SH) CAN open motor control (SH)
24 Pulse inhibit (disable) (RF) Pulse inhibit (RF)
Value Function Description