Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
116
of 208
4.3
P1184
Only external terminal JOG (MI3 to MI5 or MI7 to MI12) ZP1091 to ZP1093 or
ZP1095 to ZP1100 can be used.
When the operation mode ZP1000 = 5 (jog mode) and the jog command is „ON“, the b
maXX
®
1000 will accelerate from minimum output frequency ZP0038 to jog frequency
ZP1184. When the jog command is „OFF“, the b maXX
®
1000 will decelerate from jog
frequency to zero. The used accel/decel time is set by the jog ramp-up/ramp-down time
(ZP1182, ZP1183).
Before using the JOG command, the drive must be stopped first and operation mode
ZP1000 must be set to 5. During Jog operation, other operation commands are not ac-
cepted, except commands via the FORWARD, REVERSE and STOP keys on the digital
keypad.
Figure 51: Jog ramp-up/ramp-down time
P1184
HLG Tippbetrieb Frequenz 0.10 to 600.00 Hz
EE RFG jog frequency 6.00 Hz
ON BM_u_RFGJogFrequency 100:1 s