Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
46
of 208
4.3
P0803
The parameter determines how the motor is stopped when the b maXX
®
1000 receives
a valid stop command or detects an external fault.
Ramp: the b maXX
®
1000 decelerates to minimum output frequency (ZP0038) ac-
cording to the deceleration time and then stops.
Coast: the b maXX
®
1000 stops the output instantly upon command, and the motor
free runs until it comes to a complete standstill.
The motor stop method is usually determined by the characteristics of the motor load and
how frequently it is stopped.
1 It is recommended to use „ramp to stop“ for safety of personnel or to prevent material
from being wasted in applications where the motor has to stop after the drive is
stopped. The deceleration time has to be set accordingly.
2 If motor free running is allowed or the load inertia is large, it is recommended to select
„coast to stop“. For example: blowers, punching machines, centrifuges and pumps.
P0803
Stop Methode 0 to 3
EE Stop method 1
STOP BM_u_StopMethod 1:1 -
Value Meaning
0 STOP: ramp stop, external fault: coast stop
1 STOP: coast stop, external fault: coast stop
2 STOP: ramp stop, external fault: ramp stop
3 STOP: coast stop, external fault: ramp stop