Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
28
of 208
4.3
P0056
Not implemented.
P0057
Nominal speed of motor on motor type plate. You must set the rated speed before starting
„autotuning“. ZP0057– can be calculated with ZP0124– if only the rated slip frequency
of the motor is known. ZP0057– can be changed only if ZP0124– = 0.
P0058
Power factor (cos ϕ) of the motor.
P0061
This value should be set according to the rated frequency of the motor as indicated on the
motor type plate. Maximum voltage frequency determines the V/f curve ratio. For exam-
ple, if the drive is rated for 460 V
AC
output and the maximum voltage frequency is set to
60 Hz, the drive will maintain a constant ratio of 7.66 V/Hz (460 V/60 Hz = 7.66 V/Hz).
This parameter value must be equal to or greater than the mid-point frequency ZP0036–.
The settings have to meet the condition of ZP0039–
≤ ZP0037– ≤ ZP0053– and
ZP0038–
≤ ZP0036– ≤ ZP0061–.
Also see ZFigure 8– on page 26.
ZP0061– can be changed only if ZP0124– = 0.
P0065
Number of motor pole pairs (1 pole pair = 2 poles).
ZP0065– can be changed only if ZP0124– = 0.
P0056
Motor Nennleistung 0.00 to 99.99 kW
EE Motor nominal power 0.00 kW
STOP BM_u_MotorNomPower 100:1 -
P0057
Motor Nenndrehzahl 1 to 65535 rpm
EE Motor rated speed 1 rpm
STOP BM_u_MotorNomSpeed 1:1 rpm -
P0058
Motor Leistungsfaktor 0.6 to 1.0
EE Motor power factor 0.9
ON BM_u_MotorPowerFactor 10:1 -
P0061
Motor Nennfrequenz 0.10 to 600.00 Hz
EE Motor nominal frequency 50.00 Hz (ZP0310– = 9) or
60.00 Hz (ZP0310– = 10)
STOP BM_u_MotorNomFreq 100:1 -
P0065
Motor Polpaarzahl 1 to 10
EE Motor number of pole pairs 2
STOP BM_u_MotorPolePairs 1:1 -