P0050
Not implemented.
P0051
Not implemented.
P0053
This parameter determines the maximum output voltage of the drive. The maximum out-
put voltage setting must be smaller than or equal to the rated voltage of the motor as in-
dicated on the motor nameplate. This parameter value must be equal to or greater than
the mid-point voltage ZP0037–.
The maximum value depends on the b maXX
®
used, up to 255.0 V for single-phase de-
vices and up to 510.0 V for three-phase devices.
Also see ZFigure 8– on page 26.
P0054
Parameters ZP0054– and ZP0110– must be set if the drive is programmed to operate
in vector control mode (ZP0800– = 1). They also must be set if the „electronic thermal
overload relay“ ZP1216– or „slip compensation“ ZP0114– functions are selected.
Motor current: motor rated current in [A] on the motor.
b maXX
®
1000: rated current of used b maXX
®
1000 in [A], see parameter ZP0010–
P0050
Motor Typenschlüssel 0
hex
to FFFF
hex
EE Motor type code -
STOP BM_u_MotorType 1:1 -
P0051
Motor Seriennummer 0 to 65535
EE Motor serial number 0
STOP BM_ud_MotorSerialNr 1:1 -
P0053
Motor Nennspannung 0.1 to 255.0 V or
0.1 to 510.0 V
EE Motor rated voltage 220.0 V or 440.0 V
STOP BM_u_MotorNomVolt 10:1 V -
P0054
Motor Nennstrom 0.3*ZP0010– to 1.2*ZP0010–
EE Motor rated current ZP0010–
ON BM_u_MotorNomCurrent 10:1 -