Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
48
of 208
4.3
P0805
This parameter determines the response of the drive upon power on and operation com-
mand source is changed.
When the operation command source is from external terminal and operation command
is ON (FWD/REV DCM=closed), the b maXX
®
1000 will operate according to ZP0805–
after power is applied.
P0805
Anlaufsperre 0 to 3
EE Line start lockout 1
STOP BM_u_LineStartLockout 1:1 -
Value Meaning
0 Disable. Operation status is not changed even if operation command source ZP0802– is
changed.
1 Enable. Operation status is not changed even if operation command source ZP0802– is
changed.
2 Disable. Operation status will change if operation command source ZP0802– is changed.
3 Enable. Operation status will change if operation command source ZP0802– is changed.
ZP0805– Start lockout (Run when power is ON) Operation status when operation command
source is changed
0 Disable (b maXX
®
1000 will run) Keep previous status
1 Enable (b maXX
®
1000 doesn’t run) Keep previous status
2 Disable (b maXX
®
1000 will run) Change according to the new operation command
source
3 Enable (b maXX
®
1000 doesn’t run) Change according to the new operation command
source