Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
49
of 208
4
<For terminals FWD and REV only>
1 When ZP0805– is set to 0 or 2, the b maXX
®
1000 will run immediately.
2 When ZP0805– is set to 1 or 3, the b maXX
®
1000 will remain stopped until operation
command is received after previous operation command is cancelled.
Figure 12: P0805 Line start lockout
When the operation command source isn't from the external terminals, independently
from whether the b maXX
®
1000 runs or stops, the b maXX
®
1000 will operate according
to ZP0805– if the two conditions below are both met.
1 When operation command source is changed to external terminal (ZP0802– = 1 or 2)
2 The status of terminal and b maXX
®
1000 is different.
And the operation of the AC motor drive will be:
1 When setting 0 or 1, the status of the b maXX
®
1000 is not changed by the terminal
status.
2 When setting 2 or 3, the status of the b maXX
®
1000 is changed by the terminal status.
MI1-DCM
(close)
Power is
applied
Output
frequency
ZP0805– =
0 or 2
Output
frequency
ZP1090– =
1 or 3