Parameter list
Betriebsanleitung b maXX
®
1000
Document no. 5.07004.03
157
of 208
A
P0810 Combination of first and second master frequency
command
0 to 2 0 1:1 52
P0811 Keypad frequency command 0.00 to 600.00 Hz 50.00 Hz (ZP0310– = 9)
or
60.00 Hz (ZP0310– = 10)
100:1 Hz 52
P0812 Communication frequency command 0.00 to 600.00 Hz 50.00 Hz (ZP0310– = 9)
or
60.00 Hz (ZP0310– = 10)
100:1 52
P0813 Selections for saving keypad or communication fre-
quency
1 to 2 0 1:1 52
P0814 Initial frequency selection 0 to 2 0 1:1 53
P0815 Keypad and RS485 initial frequency setpoint 0.00 to 600.00 Hz 60.00 100:1 53
P0816 Display the master frequency command source 0 to 7 1 1:1 53
P0817 Display the operation command source 0 to 63 32 1:1 54
P0818 Auto restart after (OC or OV) fault numbers 0 to 10 0 1:1 54
P0819 Auto reset time at restart after fault 0.1 to 6000.0 s 60.0 s 10:1 54
P0820 Auto energy saving 0 to 1 0 1:1 55
P0821 Automatic voltage regulation function 0 to 3 0 1:1 55
P0822 Software braking level 370.0 to 430.0 V
DC
or 740.0 to 860.0
V
DC
380.0 V
DC
or 760.0 V
DC
10:1 56
P0823 Compensation coefficient for motor instability 0.0 to 5.0 0.0 10:1 56
P0850 Motor auto parameters auto tuning 0 to 2 0 1:1 57
P0860 Communication address RS485 1 to 254 1 1:1 58
P0861 Transmission speed RS485 0 to 3 3 1:1 58
P0862 RS485 Transmission fault treatment 0 to 3 3 1:1 58
P0863 RS485Time-out detection 0.0 to 120.0 s 0.0 s 10:1 59
P0864 RS485 Communication protocol 0 to 5 3 1:1 59
P0865 RS485 Response delay time 0 to 200 1 [2 ms] 1:1 59
P0866 USB Communication card transmission speed 0 to 4 3 1:1 60
P0867 USB Communication card protocol 0 to 5 3 1:1 60
P0868 USB Communication card transmission fault treatment 0 to 3 0 1:1 60
P0869 USB Communication card over time detection 0.0 to 120.0 s 0.0 s 10:1 61
P0870 CANopen address 1 to 127 1 1:1 61
P0871 CAN rate 0 to 5 0 1:1 62
P0890 DC braking current level 0 to 100 % 0 % 1:1 62
P0891 DC braking time during start-up 0.0 to 60.0 s 0.0 s 10:1 62
P0892 DC braking time during stopping 0.0 to 60.0 s 0.0 s 10:1 62
P0893 Start point for DC braking 0.00 to 600.00 Hz 0.00 Hz 100:1 63
P0894 Momentary power loss operation selection 0 to 2 0 1:1 63
P0895 Maximum allowable power loss time 0.1 to 5.0 s 2.0 s 10:1 64
P0896 Base-block speed search 0 to 2 1 1:1 64
P0897 Baseblock time for speed search (BB) 0.1 to 5.0 s 0.5 s 10:1 66
P0898 Current limit for speed search 30 to 200 % 150 % 1:1 66
P0908 Accel/decel rate of change of UP/DOWN operation
with constant speed
0.01 to 10.00 Hz/2
ms
0.01 Hz / 2 ms 100:1 67
Parameter Range Standard value Internal
standard-
ization
Page