Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
56
of 208
4.3
When the motor ramps to stop, the deceleration time is longer. When setting this param-
eter to 2 with auto acceleration/deceleration, the deceleration will be quicker.
P0822
This parameter sets the DC link voltage at which the brake chopper is activated.
The maximum value depends on the b maXX
®
used, up to 430.0 V
DC
for single-phase
devices and up to 860.0 V
DC
for three-phase devices.
This parameter is invalid for b maXX
®
BM1x1x
models without brake chopper.
P0823
The drift current will occur in a specific zone of the motor and it will make motor instable.
By using this parameter, it will improve this situation greatly.
The drift current zone of the high-power motors is usually in the low frequency area.
It is recommended to set to more than 2.0.
Value Meaning
0 AVR function enabled
1 AVR function disabled
2 AVR function disabled for deceleration
3 AVR function disabled for stop
P0822
Bremsschwelle Zwischenkreis 370.0 to 430.0 V
DC
or
740.0 to 860.0 V
DC
EE Software braking level 380.0 V
DC
or 760.0 V
DC
STOP BM_u_SoftBrakLevel 10:1 -
P0823
Kompensationsfaktor der Motorinstabilität 0.0 to 5.0
EE Compensation coefficient for motor instability 0.0
ON BM_u_CompCoeffMotorInstab 10:1 -
Value Meaning
0.0 Disabled
0.1 to 5.0 Recommended 2.0