Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
51
of 208
4
P0807
This parameter sets the up/down mode only for external terminals.
This parameter determines the increase/decrease of the motor frequency when operated
via the multi function inputs (ZP1091– to ZP1094– are set to 10 (up command) or 11
(down command).
P0809
This parameter set the master frequency command source of the b maXX
®
1000.
The factory setting for master frequency command is 1 (digital keypad is optional).
Setting 2:
use the ACI/AVI switch on the b maXX
®
1000 to select ACI or AVI2. When setting to AVI,
AVI2 is indicated.
When the b maXX
®
1000 is controlled by external terminal, please refer to ZP0805– for
details.
The first/second frequency/operation command is enabled/disabled by multi function in-
put terminals. Please refer to ZP1091– to ZP1094–.
P0807
Hochlauf/Rücklauf Mode 0 to 3
EE Up/Down Mode 0
STOP BM_u_UpDownMode 1:1 -
Value Meaning
0 By digital keypad up/down keys mode
1 Based on acceleration/deceleration time according to ZP1172–, ZP1173–, ZP1180–,
ZP1181–
2 Constant speed (according to ZP0908–)
3 By pulse input unit (according to ZP0908–)
P0809
Quelle der zweiten Hauptfrequenzvorgabe 1 to 255
EE Source of second master frequency command 0
ON BM_u_SourceSecondMasterFrequComm 1:1 -
Value Meaning
255 Digital terminal 15 fixed set value
0 Digital keypad UP/DOWN keys or multi-function inputs UP/DOWN.
Last used frequency saved (digital keypad is optional).
1 0 to +10V from AVI
2 4 to 20mA from ACI or 0 to +10V from AVI2
3 ProDrive communication interface
4 Digital keypad potentiometer
5 CANopen