RPC SERIES OWNER’S MANUAL
DETAILED OPERATION AND CONFIGURATION
________________________________________________________________________________
41
NOTE
: The outlet user sees only those outlets as assigned to him
by the admin user.
From the RPC > prompt, enter one of the
following commands: ON n, OFF n,
REBOOT n, where “n” is the outlet number
you want to command. Entering an outlet
number of “0” sends the command to
all
outlets.
Example: To turn “On” Outlet 3, type
ON 3
from the
RPC prompt (RPC >). The RPC responds
with:
Turn On Outlet 3 (Y/N)?
Responding “Y” for yes turns “On” Outlet 3.
Observe the status of Outlet 3 has changed
to
On
in the status menu:
Circuit Breaker : On
Selection Outlet Outlet Power
Number Name Number Status
1 OUTLET 1 1 Off
2 OUTLET 2 2 Off
3 OUTLET 3 3 Off
4 OUTLET 4 4 Off
5 OUTLET 5 5 Off
6 OUTLET 6 6 Off
7 OUTLET 7 7 Off
8 OUTLET 8 8 Off
RPC >
Likewise, typing
ON 0
at the RPC > prompt
and responding “Y” for yes, turns “On”
all
outlets. Typing
OFF n
at the RPC > prompt
turns off corresponding outlet(s).
The
REBOOT n
command will reboot or
reset equipment attached to corresponding