EasyManuals Logo

Bender ISOMETER isoRW425 User Manual

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Modbus register assignment of the ISOMETER®
54
isoRW425_D00052_03_M_XXEN / 02.2017
3025 RW
Device test dur-
ing device start
"S. Ct"
UINT 16 ---
0 = Inactive
1 = Active
3026 RW
Request stop
mode (0 = deac-
tivate device)
UINT 16 ---
0 = Stop
1 = ---
3027 RW
Alarm assign-
ment of relay 1
"r1"
UINT 16 --- Bit 11 … Bit 1
3028 RW
Alarm assign-
ment of relay 2
"r2"
UINT 16 --- Bit 11 … Bit 1
8004 WO
Factory setting
only for parame-
ters resettable by
FAC
UINT 16 --- 0x4653 "FS"
8005 WO
Start device test
UINT 16 --- 0x5445 "TE"
8006 WO
Clear fault mem-
ory
UINT 16 --- 0x434C "CL"
9800
to 9809
RO Device name
UNIT 16
(ASCII) -
refer to
Chapter
8.1.1
--- ---
9820 RO
Software
ID number
UINT 16 ---
Software D
number
Register
Permissi
ons
Description Format Unit Value range