Modbus register assignment of the ISOMETER®
53
isoRW425_D00052_03_M_XXEN / 02.2017
3018 RW
Start-up delay "t"
during device
start
UINT 16 s 0 …10
3019
RW Response delay
"ton" for relays
K1 and K2
UINT 16 s 0 … 99
3020 RW
Delay on release
"toff" for relays
K1 and K2
UINT 16 s 0 … 99
3021 RW
Repetition time
"test" for
automatic
device test
UINT 16 ---
0 = OFF
1 = 1 h
2 = 24 h
3022 RW
Parameter "Z":
Activation of
Z mode for
impedance
calculation
UINT 16
---
0 = Inactive
1 = Active
3023 RW
Parameter "Z":
System fre-
quency f
n
for Z
mode
UINT 16 ---
500 = 50.0 Hz
600 = 60.0 Hz
3024 RW
Test of the sys-
tem connection
during device
test "nEt"
UINT 16 ---
0 = Inactive
1 = Active
Register
Permissi
ons
Description Format Unit Value range