EasyManuals Logo

Bender ISOMETER isoRW425 User Manual

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Modbus register assignment of the ISOMETER®
52
isoRW425_D00052_03_M_XXEN / 02.2017
3011 RW
Alarm value
Overvoltage
"U >"
UINT 16 V U< … 500
3012 RW
Memory func-
tion for alarm
messages
(Fault memory)
"M"
UINT 16 ---
0 = Inactive
1 = Active
3013 RW
Operating mode
of relay 1 "r1"
UINT 16 ---
0 = n.o.
1 = n.c.
3014 RW
Operating mode
of relay 2 "r2"
UINT 16 ---
0 = n.o.
1 = n.c.
3015 RW Bus address
"Adr"
UINT 16 --- 0 / 3 … 90
3016 RW Baud rate "Adr 1" UINT 16 ---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
3017 RW Parity "Adr 2" UINT 16 ---
0 = 8N1
1 = 8O1
2 = 8E1
Register
Permissi
ons
Description Format Unit Value range