EasyManuals Logo

Bender ISOMETER isoRW425 User Manual

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Modbus register assignment of the ISOMETER®
51
isoRW425_D00052_03_M_XXEN / 02.2017
3004 RW
Activation
Pre-alarm value
resistance
measurement
"R1"
UINT 16 ---
0 = Inactive
1 = Active
3005 RW
Pre-alarm value
resistance
measurement
"R1"
UINT 16 k R2 … 990
3006 RW
Activation
alarm value
resistance
measurement
"R2"
UINT 16 ---
0 = Inactive
1 = Active
3007 RW
Alarm value
resistance
measurement
"R2"
UINT 16 k 1 … R1
3008 RW
Activation alarm
value
undervoltage
"U<"
UINT 16 ---
0 = Inactive
1 = Active
3009 RW
Alarm value
undervoltage UINT 16 V 10 … U>
3010 RW
Activation alarm
value
overvoltage "U>"
UINT 16 ---
0 = Inactive
1 = Active
Register
Permissi
ons
Description Format Unit Value range