Modbus register assignment of the ISOMETER®
51
isoRW425_D00052_03_M_XXEN / 02.2017
3004 RW
Activation
Pre-alarm value
resistance
measurement
"R1"
UINT 16 ---
0 = Inactive
1 = Active
3005 RW
Pre-alarm value
resistance
measurement
"R1"
UINT 16 k R2 … 990
3006 RW
Activation
alarm value
resistance
measurement
"R2"
UINT 16 ---
0 = Inactive
1 = Active
3007 RW
Alarm value
resistance
measurement
"R2"
UINT 16 k 1 … R1
3008 RW
Activation alarm
value
undervoltage
"U<"
UINT 16 ---
0 = Inactive
1 = Active
3009 RW
Alarm value
undervoltage UINT 16 V 10 … U>
3010 RW
Activation alarm
value
overvoltage "U>"
UINT 16 ---
0 = Inactive
1 = Active
Register
Permissi
ons
Description Format Unit Value range