EasyManua.ls Logo

Benning IT 110 - Testing Rcds; Limit Contact Voltage; Nominal Differential Trip-Out Current; Multiplier of Nominal Residual Current

Benning IT 110
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
Note:
- If voltage between test terminals is higher than 10 V the continuity measurement cannot be
performed.
- Before performing continuity measurement compensate test lead resistance if necessary. The
compensation is performed in LowΩfunction.
5.3 Testing RCDs (FI/RCD)
When testing RCDs, the following sub-functions can be performed:
- Contact voltage measurement
- Trip-out time measurement
- Trip-out current measurement
- RCD autotest
In general the following parameters and limits can be set when testing RCDs:
- Limit contact voltage
- Nominal differential RCD trip-out current
- Multiplier of nominal differential RCD trip-out current
- RCD type
- Test current starting polarity
5.3.1 Limit contact voltage
Safety contact voltage is limited to 50 V AC for standard domestic area. In special environments
(hospitals, wet places, etc.) contact voltages up to 25 V AC are permitted.
Limit contact voltage can be set in UC Contact voltage function only!
5.3.2 Nominal differential trip-out current
Nominal residual current is the rated trip-out current of the RCD. The following RCD current ratings
can be set: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA and 1000 mA.
5.3.3 Multiplier of nominal residual current
Selected nominal differential current can be multiplied by ½; 1; 2 or 5.
5.3.4 RCD type and test current starting polarity
The BENNING IT 110/ BENNING IT 120 B enables testing of general (non-delayed, G) and selec-
tive (time-delayed, S) RCDs, which are suited for:
- Alternating residual current (AC type, marked with
symbol)
- Pulsating DC residual current (A type, pulsed current-sensitive, marked with symbol)
- Smooth DC residual current (type B, universal current sensitive, marked with the
symbol)
For RCDs of the types A and AC, the fault current can be started with the positive half-wave at 0°
or with the negative half-wave at 180°.

Table of Contents

Related product manuals